In this paper, an automatic tuning methodology for a modified Smith predictor control scheme is proposed. The main feature of the procedure is that it is applied in closed-loop (by either evaluating a set-point or a load disturbance step response) and it is suitable for self-regulating, integral and unstable processes. Further, the process parameter estimation technique is based on the evaluation of the integral of signals, thus making it inherently robust to measurement noise. Simulation and experimental results demonstrate the effectiveness of the methodology.
An automatic tuning methodology for a unified dead-time compensator
VERONESI, Massimiliano;VISIOLI, Antonio
2014-01-01
Abstract
In this paper, an automatic tuning methodology for a modified Smith predictor control scheme is proposed. The main feature of the procedure is that it is applied in closed-loop (by either evaluating a set-point or a load disturbance step response) and it is suitable for self-regulating, integral and unstable processes. Further, the process parameter estimation technique is based on the evaluation of the integral of signals, thus making it inherently robust to measurement noise. Simulation and experimental results demonstrate the effectiveness of the methodology.File in questo prodotto: